General characteristics PUMP M05 PHCLS (related to PANEL 260202049)
Field of measurement 0-14.00 pH / 0-10.00 ppmCl2
Functions Measurement, control and adjustment of pH and free Chlorine
Resolution ±0.01 pH / ±0.01 ppmCl2
Display Backlit graphic 128×64
Accuracy ± 0.1% F.s.
Controls Keyboard (6 buttons)
Setpoint 4 clean contact relays (5 A max)
Outputs 2 proportional 4-20mA (400 W max) selectable, with galvanic separation
Hysteresis Programmable on each setpoint
Delay time Programmable on each setpoint
P.W.M. Programmable on each setpoint
Alarm Programmable on each setpoint
RS 232 (optional) RS232 connection with galvanic separation for remote control via PC
Modem (optional) Ready for GSM/GPRS connection for remote control
Flow sensor Ready with relay arrest
Datalogger Internal + external (optional SD card)
Power supply 100-240 Vac
Container In ABV V0 with IP65 protection level
Sizes 202 x 184 x 106 mm
Weight 1150 g
TYPES
Code | Description |
260202049 |
PANEL M05 PHCLs+ PS4+ FILTER+ 2 SOCKETS * |
* Panel with electric sockets, except feeder